Digital Temperature Controller Operation

Product Overview & Specifications

The controller utilizes advanced, waterproof capacitive touch keys. It regulates cooling or heating systems through a single 10A output relay. Heating is not enabled in the Icemaster G80 Glycol with Digital Control.

  • Measurement Range: -40°C to 99°C

  • Control Range: -40°C to 85°C

  • Power Supply: 220VAC ±10%, 50/60Hz

  • Power Consumption: ≤ 5W

  • Output Capacity: 10A / 220VAC (Refrigeration or Heating)

  • Sensor Input: 1x NTC Sensor (10KΩ/25°C, 2-metre cable)

Panel Display and Operation

Interface & Key Functions

The front panel features a 3-digit temperature display and 6 capacitive touch indicators.

Indicator Status

  • Key Lock LED: Illuminated when the touch panel buttons are locked.

  • Refrigeration LED: Flashes during delay or illuminates when cooling is active.

  • Defrost LED: Flashes during delay or illuminates when defrost cycle is active.

Primary Key Actions

  • Startup Temperature: Set the temperature that cooling will begin

  • Defrost key: Forced Defrost cycle (generally not required if correct glycol percentage is maintained)

  • Shutdown Temperature: Set the temperature that cooling will end

  • Up key

  • Lock/Unlock key: The interface locks automatically after 30 seconds of inactivity. Press and hold the Lock/Unlock key for 1 second to unlock the keypad

  • Down key

Setting the Desired Temperature

The control logic relies on two crucial baseline limits: Startup Temperature (the threshold where the system activates) and Shutdown Temperature (the threshold where the target temperature is hit and the system rests).

  1. Unlock the panel - hold the Unlock Key for 1 second to unlock the controller when locked.

  2. Press "Startup Temperature". Use the Up or Down keys to change the startup temperature limit.

  3. Press "Shutdown Temperature". Use the Up or Down keys to change the shutdown temperature limit.

  4. Wait 5 seconds; the controller saves settings automatically and exits to the main screen.

Example: To maintain a reservoir temperature of -5°C, set the Startup Temperature to -3°C and set the Shutdown Temperature to -5°C. This will maintain a temperature of -5°C with a 2°C hysteresis.