Operation

Grand Deluxe 3 | Operation

Operation | Dixell Controller

Front Panel Operation

Display Set Point or (in Programming Mode) select Paramater of confirm operation

Begin Manual Defrost Cycle

Increase displayed value or (in Programming Mode) cycle through displayed values

Decrease displayed value or (in Programming Mode) cycle through displayed values

Display Legend

LED
MODE
DESCRIPTION

Push theButton - this will display the current Set Point Temperature

To Adjust the Set Point Temperature

  1. Hold theButton for 3 seconds until the display shows the current Set Point and the °C or °F symbol starts flashing

  2. Use the or buttons to change the Set Point Temperature

Press theManual Defrost Button for more than 2 seconds to start a defrost cycle manually. The Defrost indicator will illuminate

The Dixell Controller has several advanced programabble features that can be tailired for individual situtations. In most ases, the default values will suit. However, as this is a commercial unit, we recommend programming the Defrost Cycle to a suitable length and interval to avoid ice build up. If ice is allowed to build up inside the compressor housing, this will negatively affect performance and potentially void warranty.

  1. Enter the Programming mode by pressing the Button and or buttons for 3 seconds. The °C or °F symbol will start flashing

  2. Select the required parameter using theor buttons

  3. When the desired parameter is displayed, press the Button to display the current stored value of the parameter

The following parameters can be selected and adjusted in Programming Mode. To adjust any parameter, enter and navigate to the desired parameter

Hysteresis is the allowed differential from the Set Point Temperature before the compressor (cooling) operates. Thus, if the Set Point Temperature is 2°C and the Hysteresis is 2°C then the compressor will operate when the internal temperature reads 4°C, and it will continue to operate until the Set Point Temperature of 2°C is reached. The default hysteresis is 2°C, which is appropriate for most circumstances.

Note: Decreasing the hysteresis can increase power consumption

  1. Enter and navigate to Hy using theor buttons

  2. The Differential Range can be adjusted between 0.1-25°C or 1-45°F. The default is 4°C

  3. Use theor buttons to change the value of the parameter to the desired Hysteresis

  4. Press the Button to store the new parameter. This will also move to the next parameter

  1. Enter and navigate to LS using theor buttons

  2. The Minimum Set Point can be adjusted down to -55°C or -67°F. The default is 0°C

  3. Use theor buttons to change the value of the parameter to the desired Minimum Set Point

  4. Press the Button to store the new parameter. This will also move to the next parameter

  1. Enter and navigate to US using theor buttons

  2. The Maximum Set Point can be adjusted up to 99°C or °F. The default is 10°C

  3. Use theor buttons to change the value of the parameter to the desired Maximum Set Point

  4. Press the Button to store the new parameter. This will also move to the next parameter

If there is a large variance between the displayed temperature (IE the temperature of the internal temperature probe and the actual internal temperature of the kegerator (as measureed by a calibrated thermometer) then the Temperature Offset can be adjusted from -9.9°C to +9.9°C

A Temperature Offset will offset the displayed temperature by the entered amount.

Thus, if the displayed temperature is 2°C but the actual internal temperature is 4°C, and offset of +2°C is required.

Note: In most cases this is not necessary to be adjusted. There will be minor temperature differences in the kegerator due to airflow etc. This may also be pre-adjusted in the factory.

  1. Enter and navigate to ot using theor buttons

  2. The Probe Calibration Offset can be adjusted from -9.9°C to +9.9°C. This may be at a value other than 0°C due to factory calibration.

  3. Use theor buttons to change the value of the parameter to the desired Probe Calibration Offset

  4. Press the

  1. Enter and navigate to CF using theor buttons

  2. Use theor buttons to cycle the display between Cesius (°C) and Fahrenheit (°F)

  3. Press the Button to store the new parameter. This will also move to the next parameter

The Grand Deluxe 3 range are commercial units. As such, they have very powerful compressors. It is important that an adequate Defrost Cycle is programmed in to ensure that ice does not build up on the cooling fins. Failure to program an adequate defrost cycle can reduce the performance of the unit and may also void warranty.

  • Enter and navigate to id using theor buttons

  • The Defrost Interval can be adjusted from 0-99 hours. The default is 6

  • Use theor buttons to change the value of the parameter to the desired Defrost Interval

  • Press the Button to store the new parameter. This will also move to the next parameter

  • Enter and navigate to Nd using theor buttons

  • The Maximum defrost length can be adjusted from 0-99 minutes. The default is 20

  • Use theor buttons to change the value of the parameter to the desired Defrost length

  • Press the Button to store the new parameter. This will also move to the next parameter

Use theor buttons to change the value of the parameter
  • Press the Button to store the new parameter. This will also move to the next parameter

  • To exit Programming Mode, press the Button and thebutton or wait for 15 seconds without pushing any buttons. This revert the controller.

  • Button to store the new parameter. This will also move to the next parameter

    On

    Compressor enabled

    Flashing

    Compressor Delay active

    On

    Defrost in progress

    Operation

    Viewing the Set Point

    Adjusting the Set Point Temperature

    Starting a manual Defrost Cycle

    Programming Mode

    Enter Programming Mode

    Adjusting Parameters

    Adjust Hysteresis

    To Adjust the Hysteresis [Hy]

    Adjust Minimum Set Point [LS]

    Adjust Maximum Set Point [US]

    Temperature Probe Calibration [ot]

    To Adjust the Temperature Probe Offset [ot]

    Change Display Units (Celsius/Fahrenheit) [CF]

    Defrost Cycle Adjustments

    Defrost Interval (interval between defrost cycles) [id]

    Maximum defrost length [Nd]

    Programming Mode
    Programming Mode
    Programming Mode
    Programming Mode
    Programming Mode
    Programming Mode
    Programming Mode
    Programming Mode

    On

    Fan enabled

    Flashing

    Fan on delay after Defrost

    OR

    On

    Current Temperature

    OR

    Flashing

    Programming Mode Active