Operation
Grand Deluxe 3 | Operation
Operation | Dixell Controller

Front Panel Operation
Display Set Point or (in Programming Mode) select Paramater of confirm operation
Begin Manual Defrost Cycle
Increase displayed value or (in Programming Mode) cycle through displayed values
Decrease displayed value or (in Programming Mode) cycle through displayed values
Display Legend
On
Compressor enabled
Flashing
Compressor Delay active
On
Defrost in progress
On
Fan enabled
Flashing
Fan on delay after Defrost
OR
On
Current Temperature
OR
Flashing
Programming Mode Active
Operation
Viewing the Set Point
Push theButton - this will display the current Set Point Temperature
Adjusting the Set Point Temperature
To Adjust the Set Point Temperature
Hold the
Button for 3 seconds until the display shows the current Set Point and the °C or °F symbol starts flashing
Use the
or
buttons to change the Set Point Temperature
Starting a manual Defrost Cycle
Press theManual Defrost Button for more than 2 seconds to start a defrost cycle manually. The Defrost indicator will illuminate
Programming Mode
The Dixell Controller has several advanced programabble features that can be tailired for individual situtations. In most ases, the default values will suit. However, as this is a commercial unit, we recommend programming the Defrost Cycle to a suitable length and interval to avoid ice build up. If ice is allowed to build up inside the compressor housing, this will negatively affect performance and potentially void warranty.
Enter Programming Mode
Enter the Programming mode by pressing the
Button and or
buttons for 3 seconds. The °C or °F symbol will start flashing
Select the required parameter using the
or
buttons
When the desired parameter is displayed, press the
Button to display the current stored value of the parameter
Use the
or
buttons to change the value of the parameter
Press the
Button to store the new parameter. This will also move to the next parameter
To exit Programming Mode, press the
Button and the
button or wait for 15 seconds without pushing any buttons. This revert the controller.
Adjusting Parameters
The following parameters can be selected and adjusted in Programming Mode. To adjust any parameter, enter Programming Mode and navigate to the desired parameter
Adjust Hysteresis
Hysteresis is the allowed differential from the Set Point Temperature before the compressor (cooling) operates. Thus, if the Set Point Temperature is 2°C and the Hysteresis is 2°C then the compressor will operate when the internal temperature reads 4°C, and it will continue to operate until the Set Point Temperature of 2°C is reached. The default hysteresis is 2°C, which is appropriate for most circumstances.
Note: Decreasing the hysteresis can increase power consumption
To Adjust the Hysteresis [Hy]
Enter Programming Mode and navigate to Hy using the
or
buttons
The Differential Range can be adjusted between 0.1-25°C or 1-45°F. The default is 4°C
Use the
or
buttons to change the value of the parameter to the desired Hysteresis
Press the
Button to store the new parameter. This will also move to the next parameter
Adjust Minimum Set Point [LS]
Enter Programming Mode and navigate to LS using the
or
buttons
The Minimum Set Point can be adjusted down to -55°C or -67°F. The default is 0°C
Use the
or
buttons to change the value of the parameter to the desired Minimum Set Point
Press the
Button to store the new parameter. This will also move to the next parameter
Adjust Maximum Set Point [US]
Enter Programming Mode and navigate to US using the
or
buttons
The Maximum Set Point can be adjusted up to 99°C or °F. The default is 10°C
Use the
or
buttons to change the value of the parameter to the desired Maximum Set Point
Press the
Button to store the new parameter. This will also move to the next parameter
Temperature Probe Calibration [ot]
If there is a large variance between the displayed temperature (IE the temperature of the internal temperature probe and the actual internal temperature of the kegerator (as measureed by a calibrated thermometer) then the Temperature Offset can be adjusted from -9.9°C to +9.9°C
A Temperature Offset will offset the displayed temperature by the entered amount.
Thus, if the displayed temperature is 2°C but the actual internal temperature is 4°C, and offset of +2°C is required.
Note: In most cases this is not necessary to be adjusted. There will be minor temperature differences in the kegerator due to airflow etc. This may also be pre-adjusted in the factory.
To Adjust the Temperature Probe Offset [ot]
Enter Programming Mode and navigate to ot using the
or
buttons
The Probe Calibration Offset can be adjusted from -9.9°C to +9.9°C. This may be at a value other than 0°C due to factory calibration.
Use the
or
buttons to change the value of the parameter to the desired Probe Calibration Offset
Press the
Button to store the new parameter. This will also move to the next parameter
Change Display Units (Celsius/Fahrenheit) [CF]
Enter Programming Mode and navigate to CF using the
or
buttons
Use the
or
buttons to cycle the display between Cesius (°C) and Fahrenheit (°F)
Press the
Button to store the new parameter. This will also move to the next parameter
Defrost Cycle Adjustments
The Grand Deluxe 3 range are commercial units. As such, they have very powerful compressors. It is important that an adequate Defrost Cycle is programmed in to ensure that ice does not build up on the cooling fins. Failure to program an adequate defrost cycle can reduce the performance of the unit and may also void warranty.
Defrost Interval (interval between defrost cycles) [id]
Enter Programming Mode and navigate to ot using the
or
buttons
The Defrost Interval can be adjusted from 0-99 hours. The default is 6
Use the
or
buttons to change the value of the parameter to the desired Defrost Interval
Press the
Button to store the new parameter. This will also move to the next parameter
Maximum defrost length [Nd]
Enter Programming Mode and navigate to ot using the
or
buttons
The Maximum defrost length can be adjusted from 0-99 minutes. The default is 20
Use the
or
buttons to change the value of the parameter to the desired Defrost length
Press the
Button to store the new parameter. This will also move to the next parameter